Description
In order to avoid rapid changes in the active power and reactive power output, the power generating system can follow after a receiving a new setpoint from grid operator / third party with the option "ramp rate limiter" a defined gradient for increasing or reducing the active power output.
Functions
The option ramp rate limiter is available for active and reactive power control.
The ramp rate limiter is applied to the grid operator / third party setpoint.
The following options are available
For active power
Ramp up | The gradient configured for ramp up only applies to the new setpoint from grid operator / third party if it's increasing the active power output. |
---|---|
Ramp up / Ramp down | Ramp-up / Ramp-down" allows you to define separate gradients ("Gradient (ramp-up)" and "Gradient (ramp-down)") for increasing and reducing the active power output. |
Soft start |
Soft start gradient will be used if the active power at the point of common coupling is ≤ 0 W. The gradient is valid until the new setpoint is reached. For example: Active power is 0 W and setpoint is 0 % => Setpoint changes from 0 % to 100 % => Soft start is active until setpoint of 100 % is reached. ( e.g. for Ramp rate 1%/s = for 100 s gradient of "Soft start" is active) |
For reactive power
Ramp rate | The gradient configured for ramp rate applies to the new setpoint from grid operator. |
---|
User Interface
Ramp rate limiter for active power
Ramp rate limiter for reactive power
Examples
Setpoint grid operator Input Signal |
Output signal |
|
---|---|---|
Ramp rate limiter off | ||
Ramp up | ||
Ramp up / Ramp down | ||
Soft start |
|